Building Enclosure logo
search
cart
facebook twitter linkedin youtube instagram Spotify Podcasts Apple Podcasts Spotify Podcasts Apple Podcasts
  • Sign In
  • Create Account
  • Sign Out
  • My Account
Building Enclosure logo
  • NEWS
    • Breaking News
  • SECTIONS
    • Columns
    • Project Profiles
    • Trade Shows
    • Sponsor Insights
  • SYSTEM DESIGNS
    • Low-Slope Roofs
    • Pitched Roofs
    • Metal Roofing Materials
    • Waterproofing
    • Sustainability
    • Insulation
    • Exterior Claddings
    • Wall Systems
    • Building Envelope
  • BLOG
    • The BE Blog
  • MEDIA
    • Podcasts
    • Webinars
    • Quiz
    • Videos
    • Polls
    • Interactive Spotlights
    • Newsletter
    • Photo Galleries
  • DIRECTORIES
    • Directory: Blue Book
    • Directory: Roofing Resource
  • PRODUCTS
  • TECHNICAL
    • Codes
      • Waterproofing
      • Roofing
    • Details
      • Waterproofing
      • Roofing
  • CONTINUING ED
  • ABOUT
    • Advertise
      • Editorial Calendar
    • Contact
    • eMag Archive Issues
  • SIGN UP!
Building EnvelopeSustainability

Basics of Building Air Leakage Rates and Pressure Differentials

Infiltration in building enclosure performance

By Daniel Overbey
graphic shows a building outline with holes
Image courtesy of author
August 27, 2025

Infiltration can be defined as outdoor airflow into a building through unintentional openings, such as cracks, and exterior entry or exit doors. Infiltration can have a major impact on building energy use and indoor air quality (IAQ) by allowing unconditioned and unfiltered air to penetrate a thermal enclosure. According to the U. S. Department of Energy, infiltration accounts for around 6 percent of the energy use for commercial buildings.

Several model codes, standards, and certification systems seek to reduce infiltration in buildings by requiring air leakage compliance through on-site third party testing. For instance:

  • ANSI/ASHRAE/IES Standard 90.1-2022 requires a maximum air leakage rate of 0.35 cubic feet per minute per square foot (CFM/ft²) [1.8 liters per second per square meter (L/s m²)] of the building thermal envelope area at a pressure differential of 75 pascals (ref. 5.4.3.1.4).
  • 2024 International Energy Conservation Code (2024 IECC) generally requires a maximum air leakage rate of 0.35 CFM/ft² [1.8 L/s m²] of the building thermal envelope area at a pressure differential of 75 pascals (ref. C402.6.2).
  • 2024 International Green Construction Code (2024 IgCC) requires air testing at 75 pascals such that corrective measures are required for any building with air leakage exceeding 0.35 CFM/ft² [1.8 L/s m²] (ref. 1001.6).
  • 2021 Phius CORE Standard sets a pass/fail certification requirement on airtightness. Full building pressurization and depressurization tests are required to demonstrate compliance. For most projects, the threshold is 0.060 CFM/ft² [0.03 L/s m²] at 50 pascals (exact requirements and protocol may vary).

Dealing with geometries and volumes day-in and day-out, a building design and construction professional can likely conceptualize the concept of cubic feet per minute of air leakage. So, a notion such as 0.35 cubic feet per minute for every square foot of the building thermal envelope is visceral enough. 

But what about that "75 Pascals" or "50 Pascals" part? 

Eh. Close enough, right?

No. The pascal is critically important when it comes to infiltration—and ignoring it can lead professionals far astray.

 

Air Pressure and Pascals

The pascal (Pa) is a unit of measure for pressure and stress. 

Imagine standing in front of a table and pressing down on it with your hand. Your hand would be exerting pascals on the table. 

Named in honor of French philosopher and scientist Blaise Pascal (1623-1662), one pascal equals the pressure of one newton per square meter [one kilogram per meter per second squared]. Moreover, a newton is named after English physicist and mathematician Isaac Newton (1642-1727) in recognition of his work on mechanics, specifically his second law of motion.

In other words:

In I-P units: 1 Pa = 1 N/m²

In SI units: 1 Pa = 1 kg/(m × s²)

Pascals are very small and therefore the kilopascal (kPa) of 1,000 N/m² is more commonly used.

For context, standard atmospheric pressure (or 1 atm) is defined as 101.325 kPa. This pressure decreases exponentially with height as there is less air pressing down from above.

To bring it back to Earth, one pound per square inch of pressure equals 6.895 kPa.

 

Pascals and Room Pressurization in Buildings

What does this mean for buildings?

Room pressurization uses pressure differentials, measured in Pascals, to control airflow and prevent contaminants from entering or escaping a room. A room is positively pressurized by supplying air with an HVAC system to create a slight pressure difference, typically ranging form +5 to +20 Pa, which forces air outwards through controlled openings like door gaps, establishing a barrier to pollutants.

Due to fire safety considerations, stairwells and refuge areas are usually kept at a slightly higher pressure than the typical rooms across various floors. This higher pressure (e.g., +25 to +50 Pa) helps to prevent smoke from seeping into escape routes, keeping them safe for evacuation and for firefighters to enter.

As a matter of course, if a room is negatively pressurized, likewise typically ranging form -5  to -20 Pa, it will "pull" air into it.

If operating close to neutral pressurization, differentials of ±1 to 2 Pa, sometimes higher at around 4 or 5 Pa, may be exhibited between rooms or HVAC zones.

Pascal readings taken with a micromanometer can verify the degree to which a room is operating compared to adjacent spaces.

 

Building Envelope and Air Leakage Testing

This gets us back around to those codified maximum air leakage rates using field testing.

Field testing can be conducted to quantify the air leakage of a building envelope. The testing can be conducted using some sort of fan-based depressurization. In such an approach, air is extracted from the building's conditioned spaces using a portable exhaust fan. This controlled air exhaust results in a negative air pressure within the building relative to the exterior (this is known as depressurization). 

The amount of air exhausted from the building's interior is increased until a standard reference negative air pressure is achieved. Conventionally, this standard reference negative air pressure is 50 pascals—though, 75 pascals is also common. 

The amount of air necessary to be exhausted from the building's interior in order to depressurize the unit to the reference negative pressure can be measured. The leakier the building envelope, the greater the amount of air required to depressurize the building to the reference pressure. This amount can be averaged across the entire thermal enclosure on a per unit area basis. 

For instance, if a building's tested average air leakage rate at a pressure differential of 75 pascals is 0.35 CFM/ft² [1.8 L/s m²] or lower, then it complies with Standard 90.1-2022 and 2024 IECC. If the rate is greater, then corrective measures should be taken to tighten up the building's air barrier.

How much pressure is 50 or 75 pascals?

50 Pa ≈ 0.2 inches of water

75 Pa ≈ 0.3 inches of water

This is important to note. It might not seem like much, but 75 pascals is about 50% more pressure than 50 pascals.

 

Assessing Infiltration in Energy Modeling Tools

Building performance simulation (BPS) tools will consider some degree of infiltration as part of a whole-building energy analysis. Often, users will be prompted to approximate their project's air leakage as a flow rate per area of the thermal envelope such as CFM/ft² [m³/h per m²].

It is critical to understand what air pressure differential is assumed for the air leakage input.

While some BPS platforms may utilize methodologies that assume air leakage rates at 50 Pa or 75 Pa, others may not. For instance, some BPS platforms use EN 15242:2007 Ventilation for Buildings - Calculation Methods for the Determination of Air Flow Rates in Buildings Including Infiltration. This European Standard describes the method to calculate the ventilation air flow rates for buildings to be used for applications such as energy calculations, heat and cooling load calculation, summer comfort and indoor air quality evaluation—and it assumes a neutral pressurization of 4 Pa.

Since the same building will exhibit different infiltration rates at different pressures, this is critical.

When a building's air leakage rate is assessed during, say, a blower door test, the rate is measured at 50 Pa or 75 Pa. An energy analysis tool assuming "normal" operating conditions will assume a pressure of 2 Pa or 4 Pa—under such conditions, the air leakage rate will be far different.

 

Converting Air Leakage Rates to Account for Different Pascals

I want to tip my hat to Patrick Chopson at cove, who brought to my attention that one can convert between different pressures the power law equation can be utilized.

For instance, if one needed to convert between an infiltration rate (CFM/ft²) at 75 Pa to 4 Pa, then apply:

(infiltration@4 Pa) = (infiltration@75 Pa) × (4/75)^0.65

The pressure exponent of 0.65 is a typical value for all buildings; however, if fan pressurization test data is available, the building's specific value may be used. 

Let us apply 0.35 CFM/ft² at 75 Pa:

infiltration@4 Pa =  0.35 × (0.053)^0.65

infiltration@4 Pa =  0.05 CFM/ft² 

For reference, below is a tabulation of typical infiltration rates from EN 15242:2007 Annex B, converted from 4 Pa to 50 Pa and 75 Pa.

chart shows air leakage rates at various pressure differentialsDefault air leakage rates at various pressure differentials. Figure by Daniel Overbey.


KEYWORDS: ANSI (American National Standards Institute) ASHRAE building codes building envelope building envelope design green building leaking testing

Share This Story

Overbey   head shot 2020 3

Daniel Overbey, AIA, NCARB, LEED Fellow (LEED AP BD+C, ID+C, O+M), WELL AP is an Assistant Professor of Architecture at Ball State University and the Director of Sustainability for Browning Day in Indianapolis, Ind. His work focuses on high-performance building design and construction, environmental systems research, green building certification services, energy/life-cycle assessment modeling, and resilient design. He can be reached at djoverbey@bsu.edu.

Recent Comments

These are actually very helpful tips. It is...

This is the most beneficial blog for all...

This blog is a great resource for anyone...

Thank you for sharing this important information. I...

This is a very interesting subject of the...

Manage My Account
  • Sign up for the Newsletter
  • Online Registration
  • Manage My Preferences
  • Registration Customer Service

More Videos

Sponsored Content

Sponsored Content is a special paid section where industry companies provide high quality, objective, non-commercial content around topics of interest to the Building Enclosure audience. All Sponsored Content is supplied by the advertising company and any opinions expressed in this article are those of the author and not necessarily reflect the views of Building Enclosure or its parent company, BNP Media. Interested in participating in our Sponsored Content section? Contact your local rep!

close
  • HITT Construction headquarters
    Sponsored byBuilding Composites® LLC

    Pushing the Envelope

  • 2 construction workers and a DEXcell panel
    Sponsored byDEXcell Roof Boards

    Designing Low-Slope Roofs for Resilience

  • Bell Bank headquarters in Fargo, North Dakota
    Sponsored bySto Corp.

    Drained and Back-Ventilated Rainscreens vs Pressurized-Equalized Rainscreens

Popular Stories

Open vs. closed cell foam in an attic

Open-Cell vs. Closed-Cell Spray Foam

graphic shows white arrows pointing to the right on a light green background

A Breakdown of Air Leakage Testing in LEED v5 BD+C

graphic shows a building destoryed by tornados with information on the amount of torandos in 2026 in the US

Record-Breaking Tornado Activity in Illinois Signals New Challenges for Architects

Building Enclosure Newsletter

BE Poll

Events

April 9, 2026

Strategies for High-Performance Below-Grade Waterproofing

Credits: 1 AIA LU/HSW ; 1 IIBEC CEH; 0.1 IACET CEU

On-Demand Designing a high-performance building enclosure requires more than just surface-level protection; it demands a rigorous, performance-based mastery of below-grade water and gas mitigation. This discussion will provide an expert-level analysis of below-grade waterproofing within the comprehensive framework of the high-performance building enclosure.

April 28, 2026

Roof Design Considerations That Prevent Installation Failures and Change Orders

Credit: 1 AIA LU/HSW; 1 IIBEC CEH; 0.1 ICC CEU

On-Demand This course provides visual examples of actual field conditions. Some good, some not so good; along with design suggestions that can cut installation costs and reduce construction change orders. Upon completion of this course, you will have a better understanding of the requirements the roofing contractor must meet to provide the specified roofing system warranty, and long-term value to the owner.

View All Submit An Event

Products

Plaster and Drywall Assemblies Manual

Plaster and Drywall Assemblies Manual

This is a comprehensive manual that goes beyond codes and standards, providing expert guidance in design, detailing, material selection and troubleshooting for plaster and drywall.

See More Products
×

Enhance your expertise with unparalleled insights.

Join thousands of building professionals today. Shouldn’t you know what they know?

SUBSCRIBE TODAY!
  • RESOURCES
    • Advertise
    • Contact Us
    • Store
    • Want More
  • SIGN UP TODAY
    • Create Account
    • Newsletter
    • Customer Service
    • Manage Preferences
  • SERVICES
    • Marketing Services
    • Reprints
    • Market Research
    • List Rental
    • Survey/Respondent Access
  • STAY CONNECTED
    • LinkedIn
    • Facebook
    • Instagram
    • YouTube
    • X
  • PRIVACY
    • PRIVACY POLICY
    • TERMS & CONDITIONS
    • DO NOT SELL MY PERSONAL INFORMATION
    • PRIVACY REQUEST
    • ACCESSIBILITY

Copyright ©2026. All Rights Reserved BNP Media, Inc. and BNP Media II, LLC.

Design, CMS, Hosting & Web Development :: ePublishing